Distinctions of PowerKureTM Solution
Voltage
Balancing Across Three Phases
Current
Balancing Across Three Phases
In-Rush
Currents
Under-voltage &
Over-voltage, Surges, Sags and Voltage Flickers
Transient, Impulses and Spikes
Suppression
Harmonics
Power Factor
Brownout Protection
Momentary Supply Interruption Protection
Description:
Most
industrial electrical loads are designed for 3 phases of current at either 480
volts or 600 volts. A 600 volt motor is optimized when it receives 3 phases of
current at 600 volts. Often, electrical systems can become destabilized and
each phase will deliver current at a different voltage such as 570, 580 and
590 volts respectively. Even minor imbalances can generate heat and electrical
losses.
Traditional Solution:
Minor
imbalances are generally left uncorrected and major imbalances are fixed by
expensive projects such as rewiring equipment and balancing loads between
phases, replacing motors and adding transformers.
PowerKureTM Solution:
|
Stabilizes voltage across all three phases using
a combination of LRC tank circuits and phase shifting reactors. In the
above example, the voltage in all three phases will be balanced to 600
volts +/- .5% to 1%. Balancing the voltage across all three phases
reduces heat and electrical losses. |
Description:
Unbalanced
loads can cause phase currents, thus creating negative voltage sequences and
circulating currents. This can result in higher equipment maintenance costs
and failures. Additionally, imbalanced loads may generate higher demand
charges from the utility if the utility is billing demand on the highest
phase.
Traditional Solution:
Minor fluctuations are generally left
un-corrected. Significant un-balanced loads can be re-wired to equalize the
load between phases.
PowerKureTM Solution:
|
Balances the load over three phases and
mitigates phase currents, thus reducing negative voltage sequences and
circulating currents. This minimizes equipment maintenance costs and
failures. Current balancing can often reduce demand charges from the
utility. |
Description:
Voltage may also fluctuate due to large inrush
currents caused by motors that draw large currents during startup.
Traditional Solution:
Minor fluctuations are generally left
uncorrected. If significant fluctuations occur additional capacitor banks can
be added and transformers tapped to higher voltages. However, traditional
capacitor banks may actually magnify the fluctuations and increase resonance
harmonics and destabilize voltage. Additionally, UPS boxes can be installed to
protect critical equipment from low voltage sags.
PowerKureTM Solution:
|
Improves voltage within each phase and decrease
fluctuations and allow motors to run more efficiently. Additionally,
PowerKureTM uses LRC tank circuits and zigzag reactors to capture and
recycle losses as needed. |
Description:
Voltage
may also fluctuate within a single phase. Depending on the loads, the phase
can be measured within a range with a maximum, a minimum and an average
voltage. Motors and equipment are designed to be most efficient at a set
voltage and any minor fluctuations, up or down, will decrease the motor’s
efficiency, generate heat and electrical losses. Significant voltage
fluctuations can cause equipment to shut down or fail.
Traditional Solution:
Minor fluctuations are generally left
uncorrected. If significant fluctuations occur, additional capacitor banks can
be added and transformers tapped to higher voltages. However, traditional
capacitor banks may actually magnify the fluctuations, increase resonance
harmonics and destabilize voltage. Additionally, UPS boxes can be installed to
protect critical equipment from low voltage sags.
PowerKureTM Solution:
|
Improves voltage within each phase and decrease
fluctuations and allow motors to run more efficiently. Additionally,
PowerKureTM uses LRC tank circuits and zigzag reactors to capture and
recycle losses as needed. |
Description:
Electrical
surges, transients and spikes, can burn out motors, harm computers and
lighting and significantly damage plant equipment.
Traditional Solution:
Traditional surge protectors chop voltage
spikes at a preset level and send them to ground.
PowerKureTM Solution:
|
Captures minor surges and recycles them
to usable energy. Extreme surges are sent to ground. |
Description:
Most AC electrical equipment in North America
is designed for AC electricity at 60 Hz or alternating cycles per second. Any
electrical current above 60Hz is called a harmonic. Harmonics are not only
wasted power but can also damage equipment.
Traditional Solution:
Traditional methods of correcting harmonics
include capturing the harmonic and sending it to ground or using power to
generate the inverse harmonic to cancel out the original harmonic.
PowerKureTM Solution:
|
Captures broadband harmonics or electrical
frequencies above 60 Hz and then recycles the wasted electricity back
to 60 Hz. This reduces electrical losses and improves equipment
longevity. |
Description:
In
alternating current (AC) systems with inductive loads, i.e. motors, the
current waveform often lags the voltage waveform. The greater the variance,
the lower the power factor, the more energy wasted. Additionally, utilities
apply a power factor penalty to electric bills if power factor drops below a
predetermined efficiency.
Traditional Solution:
The traditional method to improve power factor
is to add capacitor banks. However, capacitor banks can increase resonance,
surges, transients, harmonics, and increase KW and KWH as a result of
increased motor torque and inrush currents.
PowerKureTM Solution: